Add to Cart
Turnkey Solution 2 phase Immersion Cooling System For Bitcoin Mining
Two-phase liquid cooling:
The cooling liquid undergoes a phase change in the process of circulating heat dissipation. The cooling liquid takes away the heat from the server and then undergoes a phase change gasification. The gaseous cooling liquid is condensed by the condenser and becomes liquid again and returns to the liquid cooling tank; the cooling liquid can use 3M electronics The boiling point of the coolant FC-72 and FC-72 is above 50℃. In this case, the temperature of the water in the condensing coil does not need to be too low. The use of a dry cooler can meet the heat exchange requirements and take away the heat. The two-phase liquid cooling has a high heat transfer efficiency due to the phase change of the electronic cooling liquid. The disadvantage is that during this phase change, the electronic fluorinated liquid will escape during the vaporization process, so there is a certain degree of tightness of the container. However, it should not be too sealed to prevent the cooling system from being interrupted and the cylinder explosion event, so certain safety facilities need to be set up.
Advantages and disadvantages of dry cooler immersion cooling system
Pros:
- High build quality by necessity - Up to 98% reduction in cooling power - Long life fluid (20 years) - High cooling capacity (4kw per liter) - Equipment is dry and clean when removed - Fairly simple plumbing - Excellent scaling | Cons:
- Not ideal at small scales - Control costs are the same for 250kW and 10kW - Controls are complex and expensive - Cannot use HDDs - Tanks must be stainless - Fluids leak easily so quality control must be tightly adhered to
|
Working Diagram
Why choose us:
1) We can help buyers design specific products or produce products according to buyers' design
2) We can print logo according to buyers' requirement
3) We has exported to many countries,such as Singapore, Philippines, Vietnam, Argentina, Peru, Mongolia, Hong Kong, UAE,Russia, Poland etc.
4) Design term:We have professional design team.
5) Professional factory: We are manufacturer, specializing in manufacturing heat exchangers for over 16years, competitive price with good quality.
6) Rapid response to your needs: We will reply within 24 hours after receiving you letter. If you have urgent thing, welcome to call us.
7) The Most Efficient Service, Best Quality and Excellent Reputation.
More importantly
Shenglin and Shenglin partner can offer one-stop solution:
For bitcoin mining farm, if use immersion cooling system, Shenglin dry cooler is the most cost-effective way to remove heat and a necessary component of the immersion cooling system, We designed a full range of immersion optimized dry coolers. From 5kW single fan unit to the V-shaped 48-921kW dry coolers. Made in China, sized to your needs.
Professional system integration Customized size Thermodynamic calculations Authoritative seismic design Integrated wet curtain celdek7090 | Frame: Galvanized sheet sprayed (RAI 7035) Hot dip galvanized sheet Stainless steel plate Galvanized sheet | AC-EC fan: Protection grade ip55 Low energy consumption Inverter control High temperature resistant fan Explosion-proof fan | Various diameter fans are available: 800, 1~14 psc 910, 1~18 psc 1250, 1~8 psc 1800, 1~7 psc |
Pipe: Copper Copper nickel alloy Stainless steel Titanium | Fin: Epoxy coating Aluminum Copper: Tinned copper foil Blygold coating Stainless steel Titanium | Overhaul and cleaning: Easy to clean Optional access door or hinged fan panel Fin form for easy cleaning Robust material with high mechanical strength Easy to maintain | Different connection options: Flange connection Threaded connection Welding |
Technical Parament
D series Industrial appliaction: air conditioning, process engineering, unit-type heating/power station. It is suitable for all heat emission into air and erection in the open air.
If you want more information, more technical parament for other series, plz contact us!
Type | D2-148-4x630 | D2-166-4x630 | D2-175-4x630 | D2-228-6x630 | D2-250-6x630 | D2-276-6x630 | D2-310-8x630 | D2-343-8x630 | D2-364-8x630 | D2-392-10x630 | |||
Capacity | Water | KW | 147.99 | 165.85 | 175.21 | 227.85 | 250.42 | 276.53 | 309.85 | 342.73 | 364.07 | 391.99 | |
20% Et. Glycol | KW | 142.42 | 161.57 | 170.91 | 219.09 | 244.69 | 270.22 | 301.18 | 333.55 | 354.64 | 383.3 | ||
Air flow | M3/h | 76459 | 74341 | 72134 | 114686 | 111511 | 108188 | 152911 | 148675 | 144255 | 191136 | ||
Fan | No. X φ | 2x2x630 | 2x2x630 | 2x2x630 | 2x3x630 | 2x3x630 | 2x3x630 | 2x4x630 | 2x4x630 | 2x4x630 | 2x5x630 | ||
Fan motor | A | 20.4 | 20.4 | 20.4 | 30.6 | 30.6 | 30.6 | 40.8 | 40.8 | 40.8 | 51 | ||
400/3N/50HZ | |||||||||||||
Sound pressure level | dB(A)10m | 64 | 64 | 64 | 66 | 66 | 66 | 67 | 67 | 67 | 68 | ||
Dimension | L | mm | 2186 | 2186 | 2186 | 3250 | 3250 | 3250 | 4250 | 4250 | 4250 | 5250 | |
H | mm | 1874 | 1874 | 1874 | 1874 | 1874 | 1874 | 1874 | 1874 | 1874 | 1874 | ||
D | mm | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | ||
D1 | mm | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | ||
L1 | mm | 963 | 963 | 963 | 963 | 963 | 963 | 963 | 963 | 963 | 963 | ||
L2 | mm | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | ||
L3 | mm | 1963 | 1963 | 1963 | 2963 | 2963 | 2963 | 3963 | 3963 | 3963 | 4963 | ||
Connections inlet φ | mm | 2XDN50 | 2XDN65 | 2XDN65 | 2XDN65 | 2XDN80 | 2XDN80 | 2XDN80 | 2XDN80 | 2XDN100 | 2XDN100 | ||
Connections onlet φ | mm | 2XDN50 | 2XDN65 | 2XDN65 | 2XDN65 | 2XDN80 | 2XDN80 | 2XDN80 | 2XDN80 | 2XDN100 | 2XDN100 | ||
Product weight(empty) | kg | 769 | 811 | 853 | 1134 | 1197 | 1261 | 1498 | 1589 | 1673 | 1864 |