Add to Cart
Adiabatic Cooling Pad Systems Hybrid Double Row Fans Dry Cooler
In adiabatic cooling pad systems, cool pads(or called wet curtain) are placed in special sheet metal assemblies which are mounted in front of fin block. With the aid of the pump, water wets the pads from the upper part of the pad system. The outside air, which is dry and hot, is pre-cooled by passing it through wet cooling pads. The temperature of the air that contact with the wet cooling pads is approximated to the wet thermometer temperature. The water does not contact directly with the fins. Thus fins lifetime is longer than the direct spraying systems. Also pads prevent contamination of fins. Since the microorganisms, minerals and similar parts do not mix into the air during the evaporation phase of water, the working principle is completely healthy. The system ensures that product efficiency can be increased with minimum water consumption.
Structure:
Easy To Trasport And Install
Features of dry cooler
High efficiency heat exchanger: capacity designs for maximizing the heat transfer relative to the energy consumption of the fan. Tube and tube coupling design for low pressure drop in the coil on the media sides(maximum 100KPa at water designing condition). Our thermodynamic and aerodynamic designing software is long year tested and proved in Germany |
Fan: only choose low specific energy consumption fans. Fan nozzle designs for maximum air flow and air throw.Our fans from the world`s leading manufacturer are practically proved to be reliable in operation and long lasting. Motor: protection class IP 54 and insulation class F. Air separator for each fan. |
We facilitate you to have a long lasting and low maintainance operation. Durable material and rigid enclosure with hard gloss powder coated finish. Protective enclosure for both manifolds and U-bends. Unit design for outdoor installation. 100% leakage tested at 31bar. |
Options
Coil design refrigerant: water, oil, glycol. | Multiple circuits. |
Sub-cooling circuits. | Stainless steel or aluminum casing. |
Coated aluminum or copper fins. | Explosion proof motor. |
Customized fin spacing. |
Technical parameter
Dry cooler D2 series parameter(fin space 2.1mm)
Type | D2-148- 4x630 | D2-166- 4x630 | D2-175- 4x630 | D2-228- 6x630 | D2-250- 6x630 | D2-276- 6x630 | D2-310- 8x630 | D2-343- 8x630 | D2-364- 8x630 | D2-392- 10x630 | |||
Capacity | Water | KW | 147.99 | 165.85 | 175.21 | 227.85 | 250.42 | 276.53 | 309.85 | 342.73 | 364.07 | 391.99 | |
20% Et. Glycol | KW | 142.42 | 161.57 | 170.91 | 219.09 | 244.69 | 270.22 | 301.18 | 333.55 | 354.64 | 383.3 | ||
Air flow | M3/h | 76459 | 74341 | 72134 | 114686 | 111511 | 108188 | 152911 | 148675 | 144255 | 191136 | ||
Fan | No. X φ | 2x2x630 | 2x2x630 | 2x2x630 | 2x3x630 | 2x3x630 | 2x3x630 | 2x4x630 | 2x4x630 | 2x4x630 | 2x5x630 | ||
Fan motor | A | 20.4 | 20.4 | 20.4 | 30.6 | 30.6 | 30.6 | 40.8 | 40.8 | 40.8 | 51 | ||
400/3N/50HZ | |||||||||||||
Sound pressure level | dB(A)10m | 64 | 64 | 64 | 66 | 66 | 66 | 67 | 67 | 67 | 68 | ||
Dimension | L | mm | 2186 | 2186 | 2186 | 3250 | 3250 | 3250 | 4250 | 4250 | 4250 | 5250 | |
H | mm | 1874 | 1874 | 1874 | 1874 | 1874 | 1874 | 1874 | 1874 | 1874 | 1874 | ||
D | mm | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | ||
D1 | mm | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | ||
L1 | mm | 963 | 963 | 963 | 963 | 963 | 963 | 963 | 963 | 963 | 963 | ||
L2 | mm | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | ||
L3 | mm | 1963 | 1963 | 1963 | 2963 | 2963 | 2963 | 3963 | 3963 | 3963 | 4963 | ||
Connections inlet φ | mm | 2XDN50 | 2XDN65 | 2XDN65 | 2XDN65 | 2XDN80 | 2XDN80 | 2XDN80 | 2XDN80 | 2XDN100 | 2XDN100 | ||
Connections onlet φ | mm | 2XDN50 | 2XDN65 | 2XDN65 | 2XDN65 | 2XDN80 | 2XDN80 | 2XDN80 | 2XDN80 | 2XDN100 | 2XDN100 | ||
Product weight(empty) | kg | 769 | 811 | 853 | 1134 | 1197 | 1261 | 1498 | 1589 | 1673 | 1864 |
Why Choose us
Professional system integration Customized size Thermodynamic calculations Authoritative seismic design Integrated wet curtain celdek7090 | Frame: Galvanized sheet sprayed (rai 7035) Hot dip galvanized sheet Stainless steel plate Galvanized sheet | AC-EC fan: Protection grade ip55 Low energy consumption Inverter control High temperature resistant fan Explosion-proof fan | Various diameter fans are available: 800, 1~14 psc 910, 1~18 psc 1250, 1~8 psc 1800, 1~7 psc |
Pipe: Copper Copper nickel alloy Stainless steel Titanium | Fin: Epoxy coating Aluminum Copper: Tinned copper foil Blygold coating Stainless steel Titanium | Overhaul and cleaning: Easy to clean Optional access door or hinged fan panel Fin form for easy cleaning Robust material with high mechanical strength Easy to maintain | Different connection options: Flange connection Threaded connection Welding |
Shenglin dry cooler selection software example:
Some reference:
![]() | ![]() |
Country: USA Application: Bitcoin immersion cooling system Cooling capacity: 1270kW Cooling medium: BC-888 Supply power: 415V/3P/60Hz Fan brand: Ziehl-Abegg | Country: USA Application: Bitcoin immersion cooling system Cooling capacity: 171kW Cooling medium: bitcoin fluid Supply power: 415V/3P/60Hz Fan brand: Chinese brand |