Brand Name :Shenglin
Model Number :SHSL-D3 Series
Certification :CE
Place of Origin :China
MOQ :1
Price :660~32000 USD per unit
Payment Terms :T/T, Western Union
Supply Ability :100 units per month
Delivery Time :35~40days
Packaging Details :Stretch film and Pallet
Tube material :5/8 or 3/8 inch Copper tubes
Fin material :Can use Yellow Epoxy resin aluminum foil
Frame material :Galvanized steel plate or stainless steel
Power supply :380V/3P/50Hz or 380V/3P/60Hz
Fan brand :EBM or Ziehl-Abegg
Frame painting colour :White
Product category :Hybrid Dry Cooler
Media :Water or Ethylene glycol
Contact Now

Add to Cart

Shipping
lt's easy to get a shipping quote! Just click the button below and complete the short form.
Get Shipping Quote
View Product Description

Modular Series Wet/Dry Hybrid Adiabatic Cooling System Dry Cooler

In the Hybrid Adiabatic Cooling System there is a glycol loop and process water loop that both travel through separate dedicated pump tanks and a heat exchanger. A glycol mixture is used to prevent any possibility of freeze up of the outside coils and safeguards the system should the unit require a shut down during cold ambient conditions. The process water loop removes the potential hazards of working with glycol on your production floor by isolating it away from your process. A plate & frame heat exchanger separates the two fluids and cools the process water inside the plant. This provides an efficient process cooling solution, allows for the most water savings and increases safety with fewer chemicals required to operate your cooling system.

Normal type dry cooler features

1. High efficiency heat exchanger: capacity designs for maximizing the heat transfer relative to the energy consumption of the fan. T

2. Tube and tube coupling design for low pressure drop in the coil on the media sides(maximum 100KPa at water designing condition).

3. Our thermodynamic and aerodynamic designing software is long year tested and proved in Germany.

4. Fan: only choose low specific energy consumption fans.

5. Fan nozzle designs for maximum air flow and air throw.

6. Our fans from the world`s leading manufacturer are practically proved to be reliable in operation and long lasting.

7. Motor: protection class IP 54 and insulation class F.

8. Air separator for each fan.

9. We facilitate you to have a long lasting and low maintainance operation.

10. Durable material and rigid enclosure with hard gloss powder coated finish.

11. Protective enclosure for both manifolds and U-bends.

12. Unit design for outdoor installation. 100% leakage tested at 31bar.

Options
A. Coil design refrigerant: water, oil, glycol.

B. Multiple circuits.

C. Sub-cooling circuits.

D. Stainless steel or aluminum casing.

E. Coated aluminum or copper fins.

F. Explosion proof motor.

G. Customized fin spacing.

Technical parameter

Dry cooler D1 series parameter(fin space 2.1mm)

Type

D1-166-

4x630

D1-211-

6x630

D1-247-

6x630

D1-286-

8x630

D1-334-

8x630

D1-360-

10x630

D1-415-

10x630

D1-502-

12x630

D1-565-

14x630

D1-649-

16x630

Capacity Water 35℃ outdoor temp. Inlet 45℃, KW 165.92 211.36 247.3 286.15 334.49 359.72 415.31 502.25 565.18 649.48
outlet 40℃ Y 134.59 176.00 200.45 238.3 270.889 298.57 335.225 405.20 459.3 527.59
20% Glycol Inlet 45℃ 161.32 205.08 240.46 280.05 327.72 351.3 406.48 493.40 554.21 638.44
outlet 40℃ Y 130.96 170.87 195.07 233.18 265.64 291.81 328.48 398.45 450.87 519.13
Medium Water flow M3/h 29.00 37 43 50 58 63 72 88 98 113
Pressure drop kPa 50 70 47 97 95 92 70 97 96 95
Air flow M3/h 67455 109723 101185 146293 134908 179502 164442 197326 230584 263503
Y 51265 83661 76900 111544 102528 136437 124680 149612 174710 199665
Fan motor Phase 3 3 3 3 3 3 3 3 3 3
W 1100 16500 16500 22000 22000 27500 27500 33000 38500 44000
Y 700 10500 10500 14000 14000 17500 17500 21000 24500 28000
A 20.4 30.6 30.6 40.8 40.8 51.00 51.00 61.20 71.40 81.60
Y 12.00 18.00 18.00 24.00 24.00 30.00 30.00 36.00 42.00 48.00
Fan No X φ

2X2

X630

2x3

x630

2x3

x630

2x4

x630

2x4

x630

2x5

x630

2x5

x630

2x6

x630

2x7

x630

2x8

x630

Sound pressure level dB(A) 64 66 66 67 67 68 68 68 69 69
Y 10m 57 59 59 60 60 61 61 61 62 62
Dimension L mm 2930 4230 4230 5530 5530 6830 6830 8130 9430 10730
W mm 2100 2100 2100 2100 2100 2100 2100 2100 2100 2100
H mm 1070 1070 1070 1070 1070 1120 1120 1120 1120 1120
A mm -- -- -- -- -- -- -- -- -- --
B mm 1340 1340 1340 1340 1340 1340 1340 1340 1340 1340
C mm 1300 1300 1300 1300 1300 1300 1300 1300 1300 1300
D mm 640 640 640 640 640 640 640 640 640 640
Inlet φ mm 3” 3” 3” DN100 DN100 DN100 DN125 DN125

2X

DN125

2X

DN125

Inlet φ mm 3” 3” 3” DN100 DN100 DN100 DN125 DN125

2X

DN125

2X

DN125

Product weight(empty) kg 658 689 760 1105 1270 1320 1420 1584 1848 2112

Application:

Industrial field: process engineering, heat / power plant, power generation, chemical industry, air conditioning chiller, heat transformer, sloar system, smelting, etc.. It is suitable for all equipment which needs heat dissipation and is installed in the open air.

Packing:

Modular Series Wet/Dry Hybrid Adiabatic Cooling System Dry Cooler Modular Series Wet/Dry Hybrid Adiabatic Cooling System Dry Cooler
Modular Series Wet/Dry Hybrid Adiabatic Cooling System Dry Cooler Modular Series Wet/Dry Hybrid Adiabatic Cooling System Dry Cooler

China Modular Series Wet/Dry Hybrid Adiabatic Cooling System Dry Cooler for sale

Modular Series Wet/Dry Hybrid Adiabatic Cooling System Dry Cooler

Inquiry Cart 0