Brand Name :Shenglin
Model Number :BKFXFC series
Certification :CE
Place of Origin :China
MOQ :1 pcs
Payment Terms :T/T, Western Union
Supply Ability :1000 PCS/month
Delivery Time :18~25 days
Packaging Details :Plywood case
Compressor :Copeland EVI compressor
Air side heat exchanger type :Finned heat exchanger
Water side heat exchanger type :Shell heat exchanger
Supply power :220V 1N 50Hz
Refrigerant :R22, R407C and R410A
Working ambient temperature :-35~+43℃
Water outlet temp. :45° C
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

EVI Air Source Heat Pumps For Commercial Use

Description:

This series heat pump with advanced DC inverter and EVI technology, can save you 80% heating cost compare with the traditional heating device like gas/fuel boiler and electrical heater. It heats fast and works perfectly with the radiator and floor heater to provide you a comfortable living environment even in very cold winter. It is one of the best heating devices available today.

Features:

Twin rotary compressor with inverter control -DC inverter technology control the heat pump output according to the household`s energy requirements. Low waste of the power.
R410A refrigerant, environmentally friendly and no CO2 emissons.
Intelligent controller and LCD display.
Safelly operation with multi-protections.
Electronic expansion valve allows the accurate refrigerant go through under different workign conditions. So it ensures that the heat pump can work with high efficiency to provide enough cooling/heating capacity in any conditions.
Hydrophilic coating air heat exchanger and SWEP plate heat exchanger all available.
Auto defrosting function.
Convenient for installation and maintenance.

Optional:

Galvanized metal cabinet or stainless steel cabinet.
Refrigerant: R22, R407C and R410A
Only heating function is optional.

Technical paramater:

DC+EVI inverter heating & cooling heat pump
MODEL BKFXFC-009SMI BKFXFC-014SMI BKFXFC-018SMI
Ambient temp. range -35~+43℃ -35~+43℃ -35~+43℃
Power supply / 220V 1N~50Hz 220V 1N~50Hz 220V 1N~50Hz
Electric shock proof grade / Class I Class I Class I
Protection grade / IPX4 IPX4 IPX4
Rated cooling capacity A7W35 KW/- 7.5/2.81 11.5/2.82 14.5/2.82
Rated heating capacity A-12W41 KW/- 5.3/2.31 9.1/2.35 11.0/2.35
Heating capacity/COP A7W45 KW/- 8.8/3.60 14.5/3.56 17.5/3.40
A7W55 KW/- 8.1/2.74 14.2/2.92 16.8/2.70
A2W35 KW/- 7.3/3.45 12.0/3.54 14.0/3.54
A-15W45 KW/- 4.2/1.82 8.1/2.04 9.5/2.0
Compressor Type Scroll Scroll Scroll
Rated refrigerating input power/current KW/A 2.6/12.2 4.1/18.6 5.16/23.5
Rated heating input power/current. KW/A 2.30/11.1 3.87/17.6 4.68/21.2
Max. working current KW/A 4.40/20 6.6/30 7.5/34
Max. working pressure of heat exchanger Mpa 4.2 4.2 4.2
Temperature range of refrigeration outlet 5~15 5~15 5~15
Heat outlet temperature range 25~58 25~58 25~58
Water yield L/h 1300 2000 2500
Refrigerant type/Weight -/kg R410a/3.3 R410a/4.4 R410a/4.4
Noise dB/(A) ≤58 ≤59 ≤59
Dimension (W×D×H) mm 1090×435×900 1120×440×1360 1120×440×1360
Net weight kg 80 150 150
a: Rated cooling conditions: ambient temperature 35°C, inlet water temperature 12°C, outlet water temperature 7°C;
b: Rated heating conditions:environmental dry bulb temperature 7°C, wet bulb temperature 6°C, inlet water temperature 40°C, outlet water temperature 45°C;
c: Rated heating conditions:environmental dry bulb temperature -12°C, wet bulb temperature -14°C, outlet water temperature 41°C;
d: A7W45 Operating conditions: inlet air temperature 7°C, outlet air temperature 45°C.
Due to product improvement, above datas are subject to change without prior notice, please take the nameplate as standard.

Packing:

DC EVI Inverter Heating Cooling Air Source Heat Pumps Rooftop 2000L h DC EVI Inverter Heating Cooling Air Source Heat Pumps Rooftop 2000L h


Reference:

Country: Taiwan,China, middle school
Model: KFXR-018 UII,KFXR-045UII
Application: Domestic hot water
Country: Taiwan,China,residential building
Model: KFXR-036UII,KFXR-900UII
Application: Domestic hot water
DC EVI Inverter Heating Cooling Air Source Heat Pumps Rooftop 2000L h DC EVI Inverter Heating Cooling Air Source Heat Pumps Rooftop 2000L h
Country: Beijing, China
Model: KFXF-180 UII
Application: Breeding heating
Country: Yunan, China
Model: /
Application: Aloe drying
DC EVI Inverter Heating Cooling Air Source Heat Pumps Rooftop 2000L h DC EVI Inverter Heating Cooling Air Source Heat Pumps Rooftop 2000L h

After-Sales Service:
1. If the project needs our installation guidance, we can send our engineer and translator, but not free. We can also send customers installation video to teach them how to fix and operate with our product.

2. Usually, our product warranty is 18 months after leaving factory or 12 months after installation. within this months, all parts broken will be responsible for our factory.

Inquiry Cart 0